ABG1 series outdoor high voltage isolating switch
Previous
Next
The ABG1 series outdoor high-voltage isolating switches from Abimat Electric offering versatility with ceramic and polymer insulation pillars. Available in rating current of 200A, 400A, 630A, 800A, 1000A, and 1250A. The isolation switch can be installed with single cross arm or double cross arm. Choose between suspension or vertical mounting options for seamless integration. During installation, ensure M12 terminal bolts are securely tightened to approximately 80N·m torque by qualified personnel, ensuring reliable operation.
ABG1 series isolating switches are engineered for durability and efficiency, making them ideal for a wide range of industrial applications.
ABG1 isolating switch technical parameter:
Project | Parameter | |||||||
Rated voltage | 10kV | 12kV | 15kV | |||||
Maximum operating voltage | 12kV | 12kV | 15kV | |||||
Rated insulation level | 1minute power frequency withstand voltage (RMS) | On the ground | 40kV | 40kV | 40kV | |||
Fracture | 47kV | 47kV | 47kV | |||||
Lightning impulse withstand voltage (peak) | On the ground | 105kV | 105kV | 105kV | ||||
Fracture | 120kV | 120kV | 120kV | |||||
Rated frequency | 50Hz | |||||||
Rated current | 200A | 400A | 630A | 800A | 1000A | 1250A | ||
4seconds heat stabilized current RMS | 6.3KA | 12.5KA | 20KA | 25KA | 25KA | 31.5KA | ||
Dynamic stable current (peak) | 16KA | 31.5KA | 50KA | 63KA | 63KA | 80KA | ||
Creepage distance | 300mm | |||||||
Mechanical life | 2000times |
Contact Us:
Email: info@abimat-electric.com
WeChat: +86 18368780285